版权所有 苏ICP备14044490号-1 网站建设:中企动力 南京

Product display

Dyj-d type oil spill electrostatic controller

basic information
heat
没有此类产品
I want to inquire
Product introduction

江苏德大石化科技有限公司

江苏德大石化科技有限公司

 

The dyj-d oil-spill electrostatic controller (top mounted) can effectively prevent the overflow in the process of liquid filling. At the same time, it ensures that the resistance of the electrostatic discharge circuit between tank truck and ground pile conforms to the relevant safety standards.
 
1. Fuel oil loading system (including railway tank car and road tank car);
 
2. Sealed loading of liquid benzene and hydrocarbons;
 
3. Filling system of other chemical products;

 

江苏德大石化科技有限公司

 

System composition and functions

The dyj-d overflow electrostatic controller (top mounted) is mainly composed of the main controller, DSC electrostatic ground clamp, DOP explosion-proof sensor, DG reset board and ground wire, etc.

江苏德大石化科技有限公司1. Main controller

A. Detect the liquid level signal of DOP explosion-proof sensor and the signal of DSC electrostatic ground clamp;

B. Detect the homing sensor signal of the system and crane pipe homing sensor;

C. Drive the acoustooptic alarm to issue the acoustooptic alarm signal;

C. Output switch volume signal to the oil payment system;

 

江苏德大石化科技有限公司2.DOP explosion-proof sensor

A. Optical principle, integral safety design;

B. Convenient installation and adjustment, and the alarm height can be adjusted by locking the positioning device;

C. Wide input voltage range, full digital circuit design, strong anti-interference capability;

D. The standard distribution cable is 7 meters long (the cable length can be customized).

E. Explosion-proof tuning fork liquid level sensor is optional

江苏德大石化科技有限公司

3.DSC electrostatic ground clamp

A. special cemented carbide top;

B. Break the paint and remove the rust to ensure the car body is well grounded;

C. It can be equipped with 5 m PU straight line or 7 m PU spiral line (1 of 2 choices).

 

 

江苏德大石化科技有限公司4. DG place plate

Whether static electricity ground clamp is reset after use is the basis of standby status of the system.

 

 

 

江苏德大石化科技有限公司5. Ground wire

A. Introduce static electricity from the car body into the ground to ensure the generation of static electricity equipment

Safe ground;

B. The standard distribution cable is 3 meters long (length can be customized).

 

江苏德大石化科技有限公司6. Crane tube homing sensor (optional)

A. Collect crane pipe attitude and chain hair oil to ensure crane pipe is inserted into the tank car;

B. Interlock gear and other equipment to prevent the crane pipe from being torn off;

Technical Parameters
Explosion-proof certificate

江苏德大石化科技有限公司

 

1. The level of explosion-proof: Ex dia Ⅱ T6 Gb B
 
2. Working voltage: DC24V plus or minus 10%/AC220V plus or minus 10%(DC24V is non-polar)
 
3. Maximum working current: <200mA(DC24V power supply)
 
4. Alarm mode: acoustooptic alarm
 
5. Protection level: IP65
 
6. Response time: <1s
 
7. Working temperature: - 40 ℃ ~ + 60 ℃
 
8. Output signal: 3-way relay output, normally open and normally closed
 
9. Interface capacity: 10A,30VDC; 10. A, 250 vac
 
10. Grounding resistance alarm value: 55 Ω

 

Dyj-d overflow electrostatic controller (top mounted) mounting dimension diagram

江苏德大石化科技有限公司

江苏德大石化科技有限公司